An input is used to isolate a zone for a predetermined period then automatically reset and de- isolate

Application:
Useful for night clubs, theatres, stages etc where smoke/fog machines are used during shows.

Created: Saturday, 02 May 2020 17:02
Version: 
Size: 5.27 KB

On a reset a relay will operate for a predetermined time

Application:
Used to reset beam and flame detectors or any device that need a momentary power interruption to reset

Created: Saturday, 02 May 2020 17:04
Version: 
Size: 3.58 KB
Created: Saturday, 02 May 2020 16:52
Version: 
Size: 7.39 MB

Changing Multi-Criteria detectors (Acclimates & Intelliquads) to run in thermal only mode

Application: 

Function will force Acclimates to thermal only mode which is useful for stage shows night clubs where smoke/fog machines are used or during the day in loading docks or areas where machinery may cause unwanted alarms

Created: Saturday, 02 May 2020 17:06
Version: 
Size: 4.47 KB

Used to reannunciate a fault that has been present for x minutes

Application: 

Where the end-user requires to re-sound the panel buzzer after a set period of time to alert nearby trained staff of an acknowledged fault.

Created: Saturday, 02 May 2020 17:02
Version: 
Size: 3.53 KB

Used to momentarily interrupt power to a device to reset it

Application: 

Old beam and flame detectors latched in alarm and can only be reset by having the power toggled.

Created: Saturday, 02 May 2020 17:16
Version: 
Size: 3.57 KB

For changing setting on Acclimate/Intelliquad detectors to thermal only

Application: 

Used where shows, performances are on a regular basis. i.e. Can be pre-programmed to switch at 9:00 PM till 2:00AM everyday. Function will force Acclimates/Intelliquad to thermal only mode which is useful for stage shows night clubs where smoke/fog machines are used also doesn’t require human intervention.

Created: Saturday, 02 May 2020 17:14
Version: 
Size: 5.79 KB

Created: Saturday, 02 May 2020 16:55
Version: 
Size: 7.4 MB

When Supply Air Fans are reset the stop modules will operate for 60 seconds until the Duct probe script clears

Application: 

Script edited to have the stop modules remain inactive on an AC Reset, or panel power up

Created: Saturday, 02 May 2020 17:05
Version: 
Size: 5.39 KB

For configuring multiple detectors to participate in an Alarm Acknolwedgement scenario

Application: 

When the single occupancy unit (SOU) is large enough to have multiple detectors (usually photo-electric type) that are required to operate.

{phocadownload view=file|id=385|text=AFP-2800|target=s}{phocadownload view=file|id=492|text=AFP-3030|target=s}